| Plan Review Notes For Permit 99030524 |
| Permit Number |
99030524 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********PRVISO********************** | | | | | | NOTE SERVICE,125A+150A PANELS NEED 300A | | | METERCAN. | | | GROUND.ELECTRODE COND.TO CWP ALSO. | | | NOTE IN FUTURE OFFICE MEANS OF EGRESS TO | | | OUTSIDE210-70 | | | NOTE KITCHEN ISLAND GFI RECEPTS.REQ`D | | | ART210-52-C-2. | | | NOTE;BE SURE OF KITCHEN COUNTER REC. | | | SPACING 210-52-C-1 | | | NOTE:CODE REQ`S HWH TO BE HARDWIRED!W/ | | | MEANS OF DISC. | | | NOTE:CHECK ALL RECESSED LIGHTS TO BE | | | INSTALLED IN CLOSETS UP/DOWNSTAIRS FOR | | | PROPER CLESRANCES.ART 410-8 | | | | | | PROVISO!NEEDS TO BE DONE BEFORE ROUGH | | | INSPECTION IS CALLED!D.V.P. |
|