| 2001-01-08 00:00:00 | **************DENIED******************** | | | | | | NEED RISER DIAGRAM TO SHOW COMPLETE | | | SERVICE! | | | IF TWO SEPARATE EXIST THEN NOW THEY NEED | | | TO BE GROUPED AS PER ART. 230-72 | | | NEED NEW LOAD CALCS. DO TO ADDITIONAL | | | ELECTRICAL WORK. | | | NOTE MEANS OF EGRESS TO PORCH REQ`S | | | SWITCH FOR LIGHTING.210-70 | | | | | | **************PROVISO 6/22/99*********** | | | NEED TO SUBMIT AIC RATING FOR EQUIP. | | | AND PANEL SCHED. ART.215-5 | | | NOTE:OUTSIDE LIGHT REQ`D 210-70 | | | NOTE:NOT TO USE DISC.AS RACEWAY. |
|