| Plan Review Notes For Permit 99030450 |
| Permit Number |
99030450 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************PROVISO******************* | | | 1)ALL DUCTS PENETRATING RATED WALLS TO | | | HAVE FIRE DAMPERS UNLESS PROVISIONS OF | | | 1994 SMC 610.1.3 ARE COMPLIED WITH | | | 2) SERVICE ACCESS FOR ELECTRIC ON MECH- | | | ANICAL EQUIPMENT TO COMPLY WITH THE NAT- | | | IONAL ELECTRIC CODE (36") | | | 3) ALL AHU'S IN AREAS WITH 2000 CFM OR | | | GREATOR TO HAVE FAN SHUT DOWN BY DUCT | | | SMOKE DETECTORS WITH NOTIFICATION BY | | | BLDG FIRE ALARM OR HORN AND STROBE PER | | | 1996 NFPA 90A 4-4.4.2 OR .3 |
|