Plan Review Notes
Plan Review Notes For Permit 99030153
Permit Number 99030153
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************DENIED*****************
 1)PROVIDE OUTSIDE AIR CALCULATIONS FOR
 AREA PER ASHRAE 62-89
 2) PROVIDE AIR BALANCE SCHEDULE PER 1994
 SMC 501.2
 3) PROVISO: ALL DUCTS PENETRATING RATED
 WALLS TO BE PROTECTED PER 1994 SMC 610.1
 4) PROVISO: EXISTING DUCT TO BE INSPECT-
 ED FOR CLEANLINESS AND IF DEEMED NECESS-
 ARY, CLEANED AND SANITIZED BY LICENSED
 MECHANICAL CONTRACTOR