| 2001-01-08 00:00:00 | *************DENIED***************** | | | 1)PROVIDE OUTSIDE AIR CALCULATIONS FOR | | | AREA PER ASHRAE 62-89 | | | 2) PROVIDE AIR BALANCE SCHEDULE PER 1994 | | | SMC 501.2 | | | 3) PROVISO: ALL DUCTS PENETRATING RATED | | | WALLS TO BE PROTECTED PER 1994 SMC 610.1 | | | 4) PROVISO: EXISTING DUCT TO BE INSPECT- | | | ED FOR CLEANLINESS AND IF DEEMED NECESS- | | | ARY, CLEANED AND SANITIZED BY LICENSED | | | MECHANICAL CONTRACTOR |
|