| Plan Review Notes For Permit 99030069 |
| Permit Number |
99030069 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***********DENIED*********************** | | | AREAS SHOWN AS NOT IN CONTRACT (NIC) ON | | | MECHANICAL PLANS HAVE NO INFORMATION | | | INCLUDED FOR REVIEW.NEED SUFFICIENT | | | DETAIL TO DETERMINE HOW EXHAUST VENTS, | | | DRYER VENTS, AND REFRIGERANT LINES, ETC. | | | ARE TO BE RUN AT TIME OF BUILD OUT, I.E. | | | IS BATHROOM EXHAUST TO BE DUCTED OUT THE | | | FRONT OF THE BUILDING OR RUN OUT THROUGH | | | THE ROOF. ALSO, IS THE AIR CONDITIONING | | | FOR THESE AREAS TO BE SPLIT SYSTEMS OR | | | SOMETHING ELSE? |
|