| Plan Review Notes For Permit 99030048 |
| Permit Number |
99030048 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW PROVISO3-25-99 | | | (1) SHT.P-1 CONTACT REGIONAL SEWER TREA- | | | TMENT FOR GREASE TRAP SIZE.688-6324 | | | (2) GREASE WASTE SYSTEM TO BE DESINGED | | | PER 1994 SPC SEC 921 HORIZONTAL WASTE | | | & VENT SYSTEM,NO AUTO VENTS | | | (3) REST RM. FACILITIES TO BE SIZED FOR | | | CLUBS & LOUNGES,SERVING ALCOHOL TAB 407 | | | W/C 4 EA. M/F, LAV'S 2 EA. M/F. | | | (4)DISHWASHER & DISPOSAL TO BY PASS | | | GREASE WASTERUN TO SANITARY SEWER. | | | (5) EQUIPMENT # 54 WORK STA. ICE BIN, | | | ALL INDIRECT WASTE TO FLR SINKS. | | | (6)WOMENS REST. RM.H/C W/C NOT | | | VENTED. | | | (7) SHT P-4 GAS PIPING NOT ALLOWED BELOW | | | SLAB,UNLESS IT CAN BE REMOVED. | | | SHOW TOT. DEVELOPED LGTH. WTR. HTR | | | SUPPLY SHOULD BE 1-1/4". #6 APPL. 3/4". | | | (8) HOTEL BUSINESS REGULATION APPROVAL | | | WITH THEIR CK LIST,AT RE-SUBMITTAL. | | | END OF COMMENTS |
|