2001-01-08 00:00:00**************DENIED*****************
 1) NEED OUTSIDE AIR CALCULATIONS TO SHOW
 COMPLIANCE WITH ASHRAE 62-89(25CFM PER
 PERSON)
 2) NEED AIRBALANCE SCHEDULE PER 1994 SMC
 501.2
 3) FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRES NOTIFICATION BY HORN AND STROBE
 PER NFPA 90A 4-4.4.3
 4) PROVISO: NO COMBUSTIBLES ALLOWED IN
 THE ABOVE CEILING PLENUM SPACE PER 1994
 SMC 609.1.1