| 2001-01-08 00:00:00 | ***************DENIED******************* | | | 1) MECHANICAL PLANS SHOW INCOMPLETE DE- | | | TAILS ON DUCT SIZES AND MATERIAL. SUBMIT | | | DETAILS ON DUCTS, SIZES,AND EQUIPMENT | | | 2) PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 3) BOTH BATHROOMS IN WORK AREA REQUIRE | | | EXHAUST FANS PER 1994 SMC 503.3 | | | 4) PROVIDE INFORMATION ON EXHAUST FANS |
|