Plan Review Notes
Plan Review Notes For Permit 99021003
Permit Number 99021003
Review Stop M
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 ALL RTU'S SERVING AREAS WITH 2000 CFM OR
 GREATER SHALL HAVE FAN SHUT DOWN BY DUCT
 SMOKE DETECTOR WITH NOTIFICATION BY
 BLDG FIRE ALARM OR HORN AND STROBE PER
 NFPA 90A 4-4.4.3