| Plan Review Notes For Permit 99021003 |
| Permit Number |
99021003 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | ALL RTU'S SERVING AREAS WITH 2000 CFM OR | | | GREATER SHALL HAVE FAN SHUT DOWN BY DUCT | | | SMOKE DETECTOR WITH NOTIFICATION BY | | | BLDG FIRE ALARM OR HORN AND STROBE PER | | | NFPA 90A 4-4.4.3 |
|