| Plan Review Notes For Permit 99020854 |
| Permit Number |
99020854 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************DENIED********************* | | | | | | NOTE:2ND REVIEW.STILL NO LIGHTING SHOWN | | | FOR STORAGE AREAS AS REQ`D PER TABLE | | | 220-3B WAREHOUSES. | | | NOTE:NO ELECTRICAL RISER DIAGRAM SHOWN!! | | | NEED TO SHOW SERVICE TO INCLUDE RISER, | | | METER,PANELS,ALL CONDUITS,WIRE SIZES, | | | GROUNDING SYSTEM.FAULT CURRENT CALCULAT- | | | IONS FOR AIC RATING OF EQUIPMENT. | | | ALL THE ABOVE IS TO BE DONE AS PER ART: | | | 215-5 | | | NOTE:NEED TO SHOW LOAD CALCULATIONS AND | | | PANEL SCHEDULES. | | | NOTE:PAGENOTE MISSING RECEPTS.AS PER | | | 210-52A | | | NOTE: RECEPTS. SERVING KITCHEN COUNTER | | | ARE TO BE GFI/GFI PROTECTED AS PER ART: | | | 210-8-A-6 | | | NOTE:RECEPT.REQ`D FOR A/C COND. UNIT | | | AS PER 210-63 | | | NOTE:GROUNDING ELECTRODE CONDUCTOR TO | | | BLDG.STEEL ALSO. | | | NOTE: SMOKE DETECTORS REQ`D INSIDE AND | | | BEDROOMS AS PER NFPA-72 |
|