Plan Review Notes
Plan Review Notes For Permit 99020720
Permit Number 99020720
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**********DENIED********************
 1) NO INFORMATION INCLUDED FOR THE AIR
 HANDLING OR CONDENSING UNITS.
 2) ALL DUCTS PENETRATING RATED WALLS OR
 CEILINGS TO BE PROTECTED PER 1994 SMC
 610
 3)NEED OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 4) NEED AIR BALANCE INFORMATION PER 1994
 SMC 501.2
 5) PROVIDE INFORMATION ON EXHAUST FANS
 6)VENTILATION REQUIRED PER ASHRAE 62-89
 FOR ALL ROOMS INCLUDING STORAGE.
 7) EXHAUST DUCTS IN RATED WALLS TO BE
 PROTECTED PER 1994 610.