| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **********DENIED******************** | | | 1) NO INFORMATION INCLUDED FOR THE AIR | | | HANDLING OR CONDENSING UNITS. | | | 2) ALL DUCTS PENETRATING RATED WALLS OR | | | CEILINGS TO BE PROTECTED PER 1994 SMC | | | 610 | | | 3)NEED OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 4) NEED AIR BALANCE INFORMATION PER 1994 | | | SMC 501.2 | | | 5) PROVIDE INFORMATION ON EXHAUST FANS | | | 6)VENTILATION REQUIRED PER ASHRAE 62-89 | | | FOR ALL ROOMS INCLUDING STORAGE. | | | 7) EXHAUST DUCTS IN RATED WALLS TO BE | | | PROTECTED PER 1994 610. |
|