| Plan Review Notes For Permit 99020715 |
| Permit Number |
99020715 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | CHECKLIST - MODEL I: | | | 1-ENGINEER OF RECORD TO REVIEW ALL TRUSS | | | DRAWINGS PRIOR TO SUBMITTAL. | | | 2-ENGINEERED TRUSSES: | | | *REVISE DIMENSION OF BUILDING SHOWNN ON | | | ENGINEERED TRUSSES. | | | *CHECK MEAN ROOF HEIGHT. | | | *CLARIFY NOTE SAYING THAT IF PORCHES | | | EXIST, THEY ARE NOT EXPOSED TO WIND. | | | WHY? | | | WHAT DOES DOL STANDS FOR? DEFLECTION? | | | *REVISE DESIGN CRITERIA DATA ON TRUSS | | | LAYOUT. IT DOESN'T MATCH DESIGN | | | CRITERIA ON ENGINEERED TRUSSES. | | | *WHY NOT ALL THE ENGINEERED TRUSSES | | | SHOW THE DESIGN CRITERIA USED TO | | | DETERMINE THE LOADS?. | | | 3-CHECK/REVISE ALL HURRICANE ANCHORS | | | SPECIFIED. WILL THEY RESIST THE | | | HORIZONTAL LOADS CALCULATED BY THE | | | ENGINEERED TRUSSES? | | | 4-PROVIDE COMPLETE DETAILS AND SPECS FOR | | | ALUMINUM CEILING AT PORCH. |
|