Plan Review Notes
Plan Review Notes For Permit 99020063
Permit Number 99020063
Review Stop M
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00 
 ***************DENIED*******************
  
 1. NO INFO ON OUTSIDE AIR PER ASHRAE
 62-89
 2. ACU-1 TOTAL CFM=1850
 ACU-2 TOTAL CFM=2300
 SPEC'S FOR THESE UNITS SHOW 1585 CFM
 PER UINT SMC 104.2
 3. EF #1 DETAIL DIFFERS FROM EF #1 ON
 NOTE #5 FOR CFM FOR THIS FAN.
 4. EXHAUST AIR FROM 1ST FLOOR BATHROOM
 TO MIN. 10 FT. FROM OUTSIDE AIR
 INTAKE FOR ACU'S SMC 506.1
 5. DUCTS UNDER HOUSE TO BE A MIN. OF 4"
 ABOVE GROWN PER 1997 SMC 605.4.