| Plan Review Notes For Permit 99020063 |
| Permit Number |
99020063 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | | | | ***************DENIED******************* | | | | | | 1. NO INFO ON OUTSIDE AIR PER ASHRAE | | | 62-89 | | | 2. ACU-1 TOTAL CFM=1850 | | | ACU-2 TOTAL CFM=2300 | | | SPEC'S FOR THESE UNITS SHOW 1585 CFM | | | PER UINT SMC 104.2 | | | 3. EF #1 DETAIL DIFFERS FROM EF #1 ON | | | NOTE #5 FOR CFM FOR THIS FAN. | | | 4. EXHAUST AIR FROM 1ST FLOOR BATHROOM | | | TO MIN. 10 FT. FROM OUTSIDE AIR | | | INTAKE FOR ACU'S SMC 506.1 | | | 5. DUCTS UNDER HOUSE TO BE A MIN. OF 4" | | | ABOVE GROWN PER 1997 SMC 605.4. |
|