| Plan Review Notes For Permit 99020063 |
| Permit Number |
99020063 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1]COUNTY IMPACT FEES ARE REQUIRED | | | 2]SUBMIT MANUFACTURE SPECS.FOR CHAIRLIFT | | | 3]ALL DOORS MUST COMPLY WITH FL.ACCESS. | | | REQUIREMENT FOR MANUVERING CLEARENCES | | | SEE SECT.4.13.6 | | | 4]SUBMIT DETAIL AT FLOOR/CEILING CUT FOR | | | CHAIRLIFT | | | 5]MINIMUM CLEAR STAIR WIDTH IS 36" | | | 6]PROVIDE WIDOWS WALK DETAILS | | | 7]RECEPTION DESK MUST BE ACCESSIBLE S.A4 | | | 8]SUBMIT COMPLETE ROOF INFORMATION | | | 9]SHEET A.3,NORTH ELEVATION,PROVIDE | | | DETAIL FOR NEW CANOPY AND OPENINGS TO | | | BE FILLED IN | | | 10]PROVIDE HARDWARE SCHEDULE FOR DOORS | | | 11]SECTION 4.8.3,REQUIRES THE RAMP TO BE | | | MIN.44"CLEAR WIDTH | | | 12]SUBMIT PRODUCT TESTING FOR EXTERIOR | | | DOORS |
|