2001-01-08 00:00:00NO INFORMATION PROVIDED FOR OUTSIDE AIR
 PER ASHRAE 62-89
 ACU-1 TOTAL CFM =1850ACU-2 TOTAL CFM=
 2300SPEC'S FOR THESE UNITS SHOW 1585
 CFM PER UNIT SMC 104.2
 EF#1 DETAIL DIFFERS FROM EF#1 NOTE #5
 FOR CFM FOR THIS FAN
 EXHAUST AIR FROM 1ST FL BATHROOM TO MIN.
 10' FROM O/A INTAKE FOR ACU'S SMC 506.1
 DUCTS UNDER HOUSE TO BE MIN.4" ABOVE
 GROUND PER 1994 SMC 605.4