| Plan Review Notes For Permit 99020063 |
| Permit Number |
99020063 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | NO INFORMATION PROVIDED FOR OUTSIDE AIR | | | PER ASHRAE 62-89 | | | ACU-1 TOTAL CFM =1850ACU-2 TOTAL CFM= | | | 2300SPEC'S FOR THESE UNITS SHOW 1585 | | | CFM PER UNIT SMC 104.2 | | | EF#1 DETAIL DIFFERS FROM EF#1 NOTE #5 | | | FOR CFM FOR THIS FAN | | | EXHAUST AIR FROM 1ST FL BATHROOM TO MIN. | | | 10' FROM O/A INTAKE FOR ACU'S SMC 506.1 | | | DUCTS UNDER HOUSE TO BE MIN.4" ABOVE | | | GROUND PER 1994 SMC 605.4 |
|