Plan Review Notes
Plan Review Notes For Permit 99011147
Permit Number 99011147
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************UNSAT*******************
 1) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2) PROVIDE AIR BALANCE SCHEDULE PER 1994
 SMC 501.2
 3) FIRE DAMPERS REQUIRED AT ALL PENETRA-
 TIONS OF RATED WALLS
 4) OVERFLOW PROTECTION REQUIRED ON ALL
 UNITS PER 1994 SMC 304.8.6
 5) SERVICE ACCESS TO EQUIPMENT TO BE PER
 1994 SMC AND 1996 NEC
 (6)SHT M-2 A/C CONDENSATE TO RWL NOT
 APPROVED, RUN SEPERATE SYSTEM TO STORM
 DRAIN,DRY WELL OR PLANTER OUT SIDE OF
 BIULDING.NOTE BY PES 05-22-99