Plan Review Notes For Permit 99011127
Permit Number 99011127
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00UNSAT SHT. P-1.1 1ST FLOOR BUILDING
 DRAIN, SHOW DFU ON 4" BLDG. DRAIN.
 (2) SHT P-1.3 WTR HTR DETAIL,DIELECTRIC
 UNIONS PROHIBITED, USE DIELECTRIC
 COUPLINGS OR NIPLES.
 (2B) SAFTEY PAN TO BE LARGE ENOUGH TO
 HAVE DRAIN INSIDE OF PAN.
 (2C)TP TO BE RUN SEPERATLY SEC.507.8.4
 (2D)1" PAN DRAIN MIN. SIZE.