| Plan Review Notes For Permit 99011086 |
| Permit Number |
99011086 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************DENIED******************* | | | 1) FIRE DAMPER REQUIRED AT 18X6 RAG ON | | | AC105 PER 1994 SMC 610.1.2 | | | 2) PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 3) PROVIDE AIR BALANCE SCHEDULE PER 1994 | | | SMC 501.2 FOR PRESSURE EQUILIZATION | | | 4)PROVIDE EER INFORMATION ON MECHANICAL | | | EQUIPMENT PER FLORIDA ENERGY EFFICIENCY | | | CODE FOR BUILDING CONSTRUCTION 1997 EDIT |
|