Plan Review Notes
Plan Review Notes For Permit 99011086
Permit Number 99011086
Review Stop M
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00**************DENIED*******************
 1) FIRE DAMPER REQUIRED AT 18X6 RAG ON
 AC105 PER 1994 SMC 610.1.2
 2) PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 3) PROVIDE AIR BALANCE SCHEDULE PER 1994
 SMC 501.2 FOR PRESSURE EQUILIZATION
 4)PROVIDE EER INFORMATION ON MECHANICAL
 EQUIPMENT PER FLORIDA ENERGY EFFICIENCY
 CODE FOR BUILDING CONSTRUCTION 1997 EDIT