| 2001-03-06 00:00:00 | REVISION CHECKLIST: |
| | 1-REVISED DRAWINGS ARE VERY CONFUSING. |
| | THERE ARE OLD DRAWINGS AND NEW DWGS |
| | MIXED TOGETHER, INCLUDING ALL THE |
| | STRUCTURAL DWGS. REVISE ALL DRAWINGS ' |
| | AND DETAILS AS REQUIRED AND CLEARLY |
| | INDICATE THE DETAILS THAT REALLY APPLY |
| | TO THIS CONSTRUCTION. |
| | -SEE PLANS FOR ADDITIONAL COMMENTS. |
| | 2-ENGINEER OF RECORD TO SIGN, SEAL AND |
| | DATE ALL STRUCTURAL DRAWINGS. THERE |
| | ARE MANY STRUCTURAL DETAILS/SECTIONS |
| | SHOWN ON THE ARCHITECTURAL DRAWINGS. |
| | 3-PROVIDE PRODUCT APPROVALS FOR: |
| | -ENTRY DOORS AS SHOWN ON PLANS. |
| | -BALCONY SWING DOOR AS SHOWN ON PLANS. |
| | -SLIDING GLASS DOORS OR FRENCH DOORS |
| | WITH SIDELITES AND TRANSOM ABOVE |
| | ASSEMBLY AS SHOWN ON PLANS. |
| | NOTE: REVISE DRAWINGS TO CLARIFY WHAT |
| | TYPE OF DOORS TO BE USED. |
| | -FIXED RECTANGULAR WINDOWS WITH THE |
| | SIZES SHOWN ON ARCHITECTURAL PLANS. |
| | -ROUND AND ARCHED WINDOWS. SEE PLANS. |
| | -WINDOW MULLIONS. |
| | NOTE: WINDOWS TO HAVE MISSILE IMPACT |
| | GLAZING MUST HAVE MULLIONS TESTED FOR |
| | MISSILE IMPACT AS WELL. |
| | -ROOF TILE. |
| | 4-PROVIDE COMPLETE INSTALLATION DETAILS |
| | SHOWING CONNECTION OF WINDOWS TO STEEL |
| | COLUMNS AT BAY WINDOWS. SIGNED, SEALED |
| | AND DATED BY THE ENGINEER OF RECORD. |
| | 5-CLEARLY SPECIFY HOW TO PROTECT GAS |
| | APPLIANCE IN GARAGE. PROVIDE COMPLETE |
| | DETAIL SPECIFYING HOW ARE THE "PIPES" |
| | ATTACHED, WHAT TYPES OF PIPES? SEE |
| | COMMENTS ON PLANS. SIGNED, SEALED BY |
| | THE STRUCTURAL ENGINEER. |
| | 6-SEE COMMENTS BY THE ELECTRICAL PLAN |
| | REVIEWER. |
| | 7-CLEARLY INDICATE THE DOORS AND WINDOWS |
| | THAT ARE GOING TO HAVE MISSILE IMPACT |
| | GLAZING. |
| | -PROVIDE COMPLETE INFORMATION FOR |
| | STORM PANELS UNDER A SEPARATE PERMIT. |
| | 8-DRAWINGS SUBMITTED HAVE DOUBLE A1, A2 |
| | AND A3 SHEETS. WHY?. |
| | -MISSING SHEET A-5. |
| | 9-EXTERIOR ELEVATIONS DON'T MATCH FLOOR |
| | PLANS. REVISE AS REQUIRED. |
| | 10-PROVIDE ATTIC ACCESS AT SECOND FLOOR |
| | ROOF. SECTION 2309.6 SBC 1994. |
| | 11-PROVIDE COMPLETE SECTION/DETAIL THRU |
| | STAIRS. SIGNED, SEALED BY ENGINEER. |
| | 12-SPECIFY DRAFSTOPPING MATERIAL AND |
| | LOCATION ON SECOND FLOOR FRAMING PLAN. |
| | SECTION 2305.2.2 SBC 1994. |
| | 13-CLEARLY INDICATE ON PLANS HOW IS THE |
| | WATER DRAINED FROM TOP FLAT ROOF. |
| | SEE SECTIONS 1507, 1509.1.2.3 AND |
| | 16.4.6.2 SBC 1994. |
| | 14-SPECIFY THE DESIGN PRESSURES THAT |
| | WERE CALCULATED BY THE ENGINEER FOR |
| | ALL EXTERIOR OPENINGS. SEC 1606 SBC/94 |
| | 15-OWES $431.10 REVISIONS & RADON FEES. |
| | |
| | NOTES: |
| | -PLEASE RETURN REVIEWED SET AFTER ALL |
| | REVISIONS ARE DONE TO THE ORIGINAL |
| | DRAWINGS IN ORDER TO EXPEDITE THE |
| | REVIEW PROCESS. |
| | |