2001-01-08 00:00:00CHECKLIST:
 1-INFORMATION REQUESTED ON PROVISO HAVE
 NOT BEEN PROVIDED:
 A)PROVIDE CURRENT PRODUCT APPROVALS FOR
 EXTERIOR DOORS AND WINDOWS, WINDOW
 MULLIONS, SLIDING GLASS DOOR WITH
 TRANSOM ABOVE ASSEMBLY, ROOF TILE AND
 FLAT ROOF SYSTEM, GARAGE DOOR, ROUND
 AND ARCHED WINDOWS.
 B)PROVIDE INSTALLATION DETAILS AT THE
 CONNECTION OF WINDOWS TO STEEL COLUMN
 AT BAY WINDOWS.
 NOTE: INSTALLATION DETAILS SHALL BE
 CONSISTENT WITH SPECIFICATIONS AND
 INSTALLATION DETAILS OF WINDOW PRODUCT
 APPROVAL.
 C)PROVIDE 8" RECESS AT GARAGE AS PER
 SECTION 411.2.7 SBC 1994.
 D)CLEARLY INDICATE GLASS AREAS TO HAVE
 SAFETY GLAZING AS PER SECTION 2405.2
 SBC 1994.
 E)CLEARLY SPECIFY HOW TO PROTECT GAS
 APPLIANCE IN GARAGE. SECTION 402.7
 SGC 1994.
 2-SPECIFY SIZES OF CEILING FANS AS PER
 TABLE 6-6 FLORIDA ENERGY EFFICIENCY
 CODE FOR BUILDING CONSTRUCTION 1997 ED
 3-SEE PLANS FOR ADDITIONAL COMMENTS.
 4-SEE COMMENTS BY ELECTRICAL PLAN REVIEW
 5-STORM PANELS UNDER A SEPARATE PERMIT.
  
 PLEASE RETURN REVIEWED SET AFTER
 REVISIONS/CORRECTIONS ARE DONE IN
 ORDER TO FACILITATE AND EXPEDITE THE
 RE-REVIEW PROCESS.