| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-INFORMATION REQUESTED ON PROVISO HAVE |
| | NOT BEEN PROVIDED: |
| | A)PROVIDE CURRENT PRODUCT APPROVALS FOR |
| | EXTERIOR DOORS AND WINDOWS, WINDOW |
| | MULLIONS, SLIDING GLASS DOOR WITH |
| | TRANSOM ABOVE ASSEMBLY, ROOF TILE AND |
| | FLAT ROOF SYSTEM, GARAGE DOOR, ROUND |
| | AND ARCHED WINDOWS. |
| | B)PROVIDE INSTALLATION DETAILS AT THE |
| | CONNECTION OF WINDOWS TO STEEL COLUMN |
| | AT BAY WINDOWS. |
| | NOTE: INSTALLATION DETAILS SHALL BE |
| | CONSISTENT WITH SPECIFICATIONS AND |
| | INSTALLATION DETAILS OF WINDOW PRODUCT |
| | APPROVAL. |
| | C)PROVIDE 8" RECESS AT GARAGE AS PER |
| | SECTION 411.2.7 SBC 1994. |
| | D)CLEARLY INDICATE GLASS AREAS TO HAVE |
| | SAFETY GLAZING AS PER SECTION 2405.2 |
| | SBC 1994. |
| | E)CLEARLY SPECIFY HOW TO PROTECT GAS |
| | APPLIANCE IN GARAGE. SECTION 402.7 |
| | SGC 1994. |
| | 2-SPECIFY SIZES OF CEILING FANS AS PER |
| | TABLE 6-6 FLORIDA ENERGY EFFICIENCY |
| | CODE FOR BUILDING CONSTRUCTION 1997 ED |
| | 3-SEE PLANS FOR ADDITIONAL COMMENTS. |
| | 4-SEE COMMENTS BY ELECTRICAL PLAN REVIEW |
| | 5-STORM PANELS UNDER A SEPARATE PERMIT. |
| | |
| | PLEASE RETURN REVIEWED SET AFTER |
| | REVISIONS/CORRECTIONS ARE DONE IN |
| | ORDER TO FACILITATE AND EXPEDITE THE |
| | RE-REVIEW PROCESS. |