Plan Review Notes
Plan Review Notes For Permit 99010921
Permit Number 99010921
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00UNSAT
 (1A)SHT P-1.4 & CP-1.2 DIELECTRIC UNIONS
 PROHIBITED, USE COUPLINGS OR NIPPLES.
 (1B) TP & PRV TO BE RUN SEPERATLY.
 SEC 507.8.4
 (1C) PAN DRAIN 1" MIN.
 (1D) WTR HTR PAN TO BE LARGE ENOUGN
 FOR DRAIN TO BE INSIDE OF PAN.
 (2) SHT L1-3 POINT OF CONNECTION,BACK
 FLOW PREVENTER TO BE RED.PSI RELIEF
 VALVE ASSEMBLY.
 END OF COMMENTS