| Plan Review Notes For Permit 99010921 |
| Permit Number |
99010921 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 CLUBHOUSE | | | PROVIDE AIR BALANCE CALCULATIONS PER | | | 1994 SMC 501.2 ON CLUBHOUSE | | | NOTE #1 ON P-1.6 SHOWS CONDENSATE TO GO | | | TO SANITARY SEWER. CONDENSATE MUST GO TO | | | STORM SEWER PER CITY UTILITIES DEPT. | | | PROVISO: TERMINATE VENT ABOVE SECONDARY | | | DRAIN CONNECTION |
|