Plan Review Notes
Plan Review Notes For Permit 99010917
Permit Number 99010917
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001.PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2.PROVIDE AIR BALANCESCHEDULE PER 1994
 SMC 501.2
 3.DUCT DETECTORS TO BE TIED IN TO BLDG
 FIRE ALARM SYSTEM PER NFPA 90A 4-4.4.2
 OR IF NO BLDG SYSTEM, HORN AND STROBE
 TO BE INSTALLED FOR NOTIFICATION PER
 NFPA90A 4-4.4.3