| Plan Review Notes For Permit 99010917 |
| Permit Number |
99010917 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 2.PROVIDE AIR BALANCESCHEDULE PER 1994 | | | SMC 501.2 | | | 3.DUCT DETECTORS TO BE TIED IN TO BLDG | | | FIRE ALARM SYSTEM PER NFPA 90A 4-4.4.2 | | | OR IF NO BLDG SYSTEM, HORN AND STROBE | | | TO BE INSTALLED FOR NOTIFICATION PER | | | NFPA90A 4-4.4.3 |
|