| Plan Review Notes For Permit 99010529 |
| Permit Number |
99010529 |
|
| Review Stop |
P |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1)GAS PIPING APPEARS TO BE LOCATED IN | | | THE STAIR ENCLOSURE.THIS IS NOT | | | PERMITTED PER SBC SEC.1006.1.3, | | | 1006.1.3.1. | | | | | | 2)SUBMIT A DETAIL OF THE PROPOSED GAS | | | MANIFOLD.DETAIL TO BE SIGNED,DATED AND | | | SEALED BY PROFESSIONAL OF RECORD. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.3 | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|