| Plan Review Notes For Permit 99010529 |
| Permit Number |
99010529 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | FIRE STATS NOT ALLOWED AS INTERCHANGABLE | | | WITH DUCT SMOKE DETECTOR | | | ALL AHU'S TO HAVE OVERFLOW PROTECTION, | | | NOT JUST SUSPENDED, WERE DAMAGE COULD | | | OCCUR BY OVERFLOW OF CONDENSATE |
|