Plan Review Notes
Plan Review Notes For Permit 99010496
Permit Number 99010496
Review Stop P
Sequence Number 7
Notes
Date Text
2001-01-08 00:00:00SHT.P-6-2"ROOF DRAIN CANNOT DRAIN TO
 SANITARY SYSTEM PER SPC SEC.301.3 & CITY
 ORDINANCE.
  
 SUBMIT DOCUMENTATION FROM AIR ADMITTANCE
 VALVE MANUF.ALLOWING USE OF AAV'S ON
 CONDENSATE SYSTEM.COUNTYWIDE AMENDMENTS
 TO SPC SEC.101.4.9, 104.2.1, 303.5,
 905.7.
  
 INDIRECT WASTE PIPES SHALL DISCHARGE
 ABOVE RECEIVING RECEPTACLE AND PROVIDE
 MIN.REQD.AIR GAP PER SPC 806, 807.1.3.
  
 SHOW/NOTE TERMINATION PT. OF CONDENSATE
 DRAINS.