| Plan Review Notes For Permit 99010496 |
| Permit Number |
99010496 |
|
| Review Stop |
P |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SHT.P-6-2"ROOF DRAIN CANNOT DRAIN TO | | | SANITARY SYSTEM PER SPC SEC.301.3 & CITY | | | ORDINANCE. | | | | | | SUBMIT DOCUMENTATION FROM AIR ADMITTANCE | | | VALVE MANUF.ALLOWING USE OF AAV'S ON | | | CONDENSATE SYSTEM.COUNTYWIDE AMENDMENTS | | | TO SPC SEC.101.4.9, 104.2.1, 303.5, | | | 905.7. | | | | | | INDIRECT WASTE PIPES SHALL DISCHARGE | | | ABOVE RECEIVING RECEPTACLE AND PROVIDE | | | MIN.REQD.AIR GAP PER SPC 806, 807.1.3. | | | | | | SHOW/NOTE TERMINATION PT. OF CONDENSATE | | | DRAINS. |
|