2001-01-08 00:00:00SUBMIT CLEAR DETAIL OF ROOF SCUPPERS AND
 SHOW LOCATION OF SCUPPERS ON ROOF PLAN.
 SIZE OF SCUPPERS SHALL COMPLY W/ SPC
 APPENDIX "A",TABLE "A101.2".(PLANS DON'T
 SHOW WIDTH OF SCUPPER,ONLY 4"HT.)
  
 CLARIFY SQ.FOOTAGE DRAINED BY RAIN WATER
 LINES.ROOF PLAN AND PLBG.SHEETS DON'T
 MATCH.
  
 SHT.A14-CLEAR FLOOR SPACE UNDER H.C. LAV
 SHALL BE 29",NOT 27" AS SHOWN.SEE FACBC
 SEC.4.19.2.
  
 SHT.P-6-RAINWATER (2"R.D)CANNOT DRAIN
 INTO SANITARY SYSTEM.301.3.AND CITY ORD.
  
 SUBMIT DOCUMENTATION FROM AIR ADMITTANCE
 VALVE CO.THAT THE AAV'S CAN BE USED ON
 AN A/C CONDENSATE SYSTEM.COUNTYWIDE
 AMENDMENTS TO SPC SEC.101.4.9,104.2.1.,
 303.5,905.7.