| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** |
| | |
| | 1)NOTE!!!!! FIRST NOTE THE LAST PAGE OF |
| | NOTE SENT OUT BY THE CHIEF ELECTRICAL |
| | INSPECTOR.HIS NOTES ARE ATTACHED. |
| | WE DO HAVE RECORD OF YOU PULLING YOUR |
| | LOW VOLTAGE FOR FIRE ALARM AND FOR FOUR |
| | DATA OUTLETS. THERE IS STILL NO PERMIT |
| | PULLED FOR TELEPHONE SYSTEM. THIS MUST |
| | BE DONE!! THE PLANS ARE SHOWING TELE. |
| | |
| | |
| | 2)NOTE: PLEASE CHECK YOUR ELECTRICAL |
| | RISER DIAGRAM E-16. YOU WILL NOTE THAT |
| | YOU SHOW 7-SETS OF 500MCM FROM FPL TO |
| | MAIN GUTTER. HOWEVER LINE FROM GUTTER |
| | SHOW CONDUCTORS HOW 8-500`S ? WHICH ONE? |
| | PLEASE CORRELATE.215-5 |
| | |
| | 3)NOTE; ALSO YOU ARE SHOWING THE AIC |
| | RATINGS FOR MOST EQUIPMENT. WHAT ABOUT |
| | THESIX MAINS FROM FPL? 1OF6,2OF6,3OF6 |
| | ,,,,,ETC. IF THESE ARE FUSED DISC.S |
| | PLEASE LIST AIC RATING OF FUSES THAT ARE |
| | BEING INSTALLED. ABOVE FROM 215-5 |
| | |
| | |
| | PLEASE TAKE CARE OF THE PERMIT SITUATION |
| | AND ADDRESS THE ABOVE COMMENTS. |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL 659-8096 EXT 8372 OR THE |
| | CHIEF ELEC. INSPEC. AT EXT.8451 |