Plan Review Notes
Plan Review Notes For Permit 99010496
Permit Number 99010496
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00AIR ADMITTANCE SHALL BE INSTALLED PER
 MANUF.RECOMMENDATIONS AND SPC 905.7.
 SUPPORT DATA FROM MANUF.REQD.FOR USE ON
 CONDENSATE SYSTEMS.
  
 SLOPE OF PIPE SHALL BE MIN. OF 1/4" PER
 FT.PER SPC SEC.705.2.
  
 INDIRECT WASTE FOR COOLING TOWER SHALL
 DISCHARGE TO OPEN RECEPTACLE PER SPC
 SEC.804.5,807.2.