| Plan Review Notes For Permit 99010496 |
| Permit Number |
99010496 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | AIR ADMITTANCE SHALL BE INSTALLED PER | | | MANUF.RECOMMENDATIONS AND SPC 905.7. | | | SUPPORT DATA FROM MANUF.REQD.FOR USE ON | | | CONDENSATE SYSTEMS. | | | | | | SLOPE OF PIPE SHALL BE MIN. OF 1/4" PER | | | FT.PER SPC SEC.705.2. | | | | | | INDIRECT WASTE FOR COOLING TOWER SHALL | | | DISCHARGE TO OPEN RECEPTACLE PER SPC | | | SEC.804.5,807.2. |
|