| Date |
Text |
| 2001-01-08 00:00:00 | PROVISO: | | | ALL LOUVERED DOORS THRU RATED WALLS TO | | | BE PROTECTED BY FIRE DAMPERS IN LOUVERED | | | DOORS | | | ALL FLOOR/CEILING PENETRATIONS OF DUCTS | | | TO BE PROTECTED BY METHODS COMPLYING W/ | | | THE DESIGN OF THE ASSEMBLY OR BY CEILING | | | FLOOR DAMPERS SPECIFICALLY DESIGNED AND | | | LISTED FOR THIS TYPE SERVICE PER 1997 | | | SMC 610.2 AND 610.4 SHAFT ENCLOSURES |
|