Plan Review Notes
Plan Review Notes For Permit 99010496
Permit Number 99010496
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001ST FL "B" ZONE HAS NO AIR PATH FOR S/A
 TO GET TO E/A FAN IN OFFICE AREA
 NEED MORE COMPLETE SEQUENCE OF OPERATION
 ON SMOKE EVAC. INCL. CFM PER FLOOR
 AIR BALANCE SCHEDULE NEEDED FOR O/A TO
 EXHAUST AIR PER 1994 SMC 501.2