2001-01-08 00:00:00VACUUM PUMP DOES NOT MEET NFPA 99C REQUI
 REMENTS FOR MEDICAL VACUUM SYSTEMS. SEE
 NFPA 99C 4-8.1.1 (A) MULTIPLE PUMPS .
 (F) RECEIVERS.(G) PIPING. (I) EXHAUSTS.
 THERE ARE SEVERAL OTHER AREAS THAT COULD
 ALSO NOT MEET NFPA 99C
 MEDICAL VACUUM INSTALLATION TO COMPLY
 NFPA 99C