| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | VACUUM PUMP DOES NOT MEET NFPA 99C REQUI | | | REMENTS FOR MEDICAL VACUUM SYSTEMS. SEE | | | NFPA 99C 4-8.1.1 (A) MULTIPLE PUMPS . | | | (F) RECEIVERS.(G) PIPING. (I) EXHAUSTS. | | | THERE ARE SEVERAL OTHER AREAS THAT COULD | | | ALSO NOT MEET NFPA 99C | | | MEDICAL VACUUM INSTALLATION TO COMPLY | | | NFPA 99C |
|