Plan Review Notes
Plan Review Notes For Permit 99010297
Permit Number 99010297
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00NO VENTILATON SHOWN FOR BACK ROOM
 NO O/A CALCULATIONS PER ASHRAE 62-89
 NO AIR BALANCE SCHEDULE SHOWN SMC 501.2
 NO BATHROOM EXHAUST FANS SHOWN ON PLAN
 EXHAUST FAN REQUIRED FOR JANITOR SUPPLY
 CLOSET(MOP SINK) 1994 SMC 503.1
 FANSHUT DOWN BY DUCT SMOKE DETECTOR REQ
 W/ NOTIFICATION BY HORN AND STROBE PER
 NFPA 90A
 SEPARATE PERMITS WITH PLANS WILL BE REQ
 UIRED FOR HOOD AND FOR COOLER/FREEZER
 ABOVE ITEMS ARE PROVISO***********