| Plan Review Notes For Permit 99010297 |
| Permit Number |
99010297 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | NO VENTILATON SHOWN FOR BACK ROOM | | | NO O/A CALCULATIONS PER ASHRAE 62-89 | | | NO AIR BALANCE SCHEDULE SHOWN SMC 501.2 | | | NO BATHROOM EXHAUST FANS SHOWN ON PLAN | | | EXHAUST FAN REQUIRED FOR JANITOR SUPPLY | | | CLOSET(MOP SINK) 1994 SMC 503.1 | | | FANSHUT DOWN BY DUCT SMOKE DETECTOR REQ | | | W/ NOTIFICATION BY HORN AND STROBE PER | | | NFPA 90A | | | SEPARATE PERMITS WITH PLANS WILL BE REQ | | | UIRED FOR HOOD AND FOR COOLER/FREEZER | | | ABOVE ITEMS ARE PROVISO*********** |
|