| Plan Review Notes For Permit 98121020 |
| Permit Number |
98121020 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW 94 STD PLBG CODE | | | CONTACT PAUL SCHMITZ 561-659-8096 X8233 | | | | | | (1) SHT.PM-6 GENERAL 1.1.1.8, 3.4.1.1 | | | HUB DRAINS PROHIBITED,USE FLOOR SINKS. | | | (2) SHT P-3 GREASE TRAPS: CONTACT W. | | | PALM BCH REG. SEWER TREATMENT PLANT FOR | | | GREASE TRAP SIZE 561-686-6324 | | | (3) SHT. P-4 GAS PIPING: SHOW BTU'S OF | | | EACH APPLIANCE, TOT. BTU'S,TOT. DEVE- | | | LOPED LENTH, ISOMETRIC DRWG. | | | (4) SHT P-5 SAFE WASTEPROHIBITED,USE | | | HORIZONTAL WASTE & VENT,SPC SEC 921. | | | (5) A/C CONDENSATE: TO STORM DRAIN, DRY | | | WELL, OR PLANTER,NOT TO SANITARY SEWER. | | | (6) DISH WASHER TO SANITARY SEWER. | | | (7) SHT P-7 DETAIL 4 SANITIZER SYSTEM: | | | WATTS #7 BFP NOT APPROVED, USE WATTS | | | 36N ANTI SYPHON DEVICE. | | | (8) DETAIL 12 FOOD PREPARATION SINK: EA. | | | COMPARTMENT WASTE TO HAVE A SEPERATE | | | WASTE TO FLOOR SINK. | | | (9) DISH WASHERS TO BY PASS GREASE TRAP. | | | END OF COMMENTS | | | PERMIT ISSUED WIHH PROVISO SEE LIST | | | 03-04-99PES |
|