2001-01-08 00:00:00PLUMBING PLAN REVIEW 94 STD PLBG CODE
 CONTACT PAUL SCHMITZ 561-659-8096 X8233
  
 (1) SHT.PM-6 GENERAL 1.1.1.8, 3.4.1.1
 HUB DRAINS PROHIBITED,USE FLOOR SINKS.
 (2) SHT P-3 GREASE TRAPS: CONTACT W.
 PALM BCH REG. SEWER TREATMENT PLANT FOR
 GREASE TRAP SIZE 561-686-6324
 (3) SHT. P-4 GAS PIPING: SHOW BTU'S OF
 EACH APPLIANCE, TOT. BTU'S,TOT. DEVE-
 LOPED LENTH, ISOMETRIC DRWG.
 (4) SHT P-5 SAFE WASTEPROHIBITED,USE
 HORIZONTAL WASTE & VENT,SPC SEC 921.
 (5) A/C CONDENSATE: TO STORM DRAIN, DRY
 WELL, OR PLANTER,NOT TO SANITARY SEWER.
 (6) DISH WASHER TO SANITARY SEWER.
 (7) SHT P-7 DETAIL 4 SANITIZER SYSTEM:
 WATTS #7 BFP NOT APPROVED, USE WATTS
 36N ANTI SYPHON DEVICE.
 (8) DETAIL 12 FOOD PREPARATION SINK: EA.
 COMPARTMENT WASTE TO HAVE A SEPERATE
 WASTE TO FLOOR SINK.
 (9) DISH WASHERS TO BY PASS GREASE TRAP.
 END OF COMMENTS
 PERMIT ISSUED WIHH PROVISO SEE LIST