| 2001-01-08 00:00:00 | PROVISO:SEPARATE PERMITS REQUIRED FOR | | | HOOD AND SUPPRESSION SYSTEM FOR HOOD | | | 2) EXISTING DUCTS TO BE REUSED TO BE INS | | | PECTED FOR CLEANLINESS AND CLEANED AND | | | SANITIZED BY LICENSED MECH. CONTRACTOR | | | 3) CEILING DIFFUSERS IN RATED CEILING TO | | | BE RADIANT TYPE-RATED DIFFUSERS,SEE A-8 | | | DETAIL 4 | | | 4) MACHINERY ROOMS ON ROOF TO BE VENTI- | | | LATED AND PROTECTED PER 1994 SMC CH.11, | | | INCLUDING LEVEL 1 MACHINE ROOM 1105 |
|