| 2001-04-18 00:00:00 | SITE PLANS DENIED; | | | | | | NOT ENOUGH INFORMATION; | | | | | | 1.WHAT SIZE ARE GREASE TRAPS? | | | | | | 2.WHY IS THERE 3 GREASE TRAPS? | | | | | | 3.GREASE TRAPS SHALL BE REVIEW AND | | | APPROVED BY THE UTILITY DEPARTMENT. | | | CALL RODNEY COMPO AT 837-4074. | | | | | | 4.TWO WAY CLEANOUTS ARE REQUIRED BETWEEN | | | EACH TANK AND AT THE FRONT OF THE | | | FIRSTTANK AND AFTER THE LAST TANK. | | | | | | 5.WHY IS SEWER AND WATER TIDED INTO TWO | | | BUILDINGS? EACH BUILDING SHOULD HAVE | | | ITS OWN HOOKUP. | | | | | | 6.NEED CAULKULATIONS FOR STORM DRAINAGE | | | PIPING.PLEASE SHOW SQUIRE FOOTAGE TO | | | BE DRAINED. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8377 OR 8369 |
|