| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NEED OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 2) NEED AIR BALANCE SCHEDULE PER 1994 | | | SMC 501.2 | | | 3) FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | REQUIRED PER 1994 SMC 406.1 | | | 3A) NOTIFICATION TO BE PER 1996 NFPA 90A | | | 4-4.4.2 OR 4-4.4.3 STOBE AND HORN | | | 4) SECOND FLOOR DUCT TO BE INSULATED W/ | | | R-6 PER FLORIDA ENERGY EFFICIENCY CODE | | | 1997, UNLESS ROOF IS INSULATED TO R-16 | | | 5) ROOF PLAN DOES NOT SHOW EXHAUST FAN | | | TERMINATION LOCATION |
|