Plan Review Notes
Plan Review Notes For Permit 98120860
Permit Number 98120860
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) NEED OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 2) NEED AIR BALANCE SCHEDULE PER 1994
 SMC 501.2
 3) FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED PER 1994 SMC 406.1
 3A) NOTIFICATION TO BE PER 1996 NFPA 90A
 4-4.4.2 OR 4-4.4.3 STOBE AND HORN
 4) SECOND FLOOR DUCT TO BE INSULATED W/
 R-6 PER FLORIDA ENERGY EFFICIENCY CODE
 1997, UNLESS ROOF IS INSULATED TO R-16
 5) ROOF PLAN DOES NOT SHOW EXHAUST FAN
 TERMINATION LOCATION