| 2001-04-20 00:00:00 | FAILED: |
| | 1. PLEASE PROVIDE ITEMS AS INDICATED ON |
| | ATTACHED SHEET FOR STORM WATER |
| | CONSTRUCTIONS TO, JOSE DEL RIO, STORM |
| | WATER ENGINEER, 1000 45TH STREET WEST |
| | PALM BEACH, FL 33407 561-659-8040. |
| | 2. PLEASE STATE IF GARBAGE IS TO BE |
| | PICKED UP BY THE CITY OR IF IT IS |
| | PRIVATE PICKUP.CITY PICKUP THEN THE |
| | FOLLOWING REQUIREMENTS MUST BE MET.SEE |
| | ATTACHED |
| | 3. THE "APPLICATION FOR CONSTRUCTION |
| | WITHIN PUBLIC R.O.W" MUST BE SUBMITTED |
| | TO CITY ENGINEER, RICHARD PITTMAN |
| | 100045TH STREET WEST PALM BEACH, FL |
| | 33407 561-569-8040. SEE ATTACHED |
| | 4. A SEPARATE PERMIT FOR UNDERGROUND |
| | UTILITIES CONSTRUCTION MAY BE REQUIRED. |
| | PLEASE CONTACT, DEAN RUNNELS LIC./PER. |
| | SUPERVISOR, 200 2ND STREET WEST PALM |
| | BEACH, FL 33407561- 659-8040 EXT. 8496 |
| | 5. PLEASE CONTACT RODNEY COMPO UTILITIES |
| | TECHNICIAN ( INDUSTRIAL PRETRETMENT ) |
| | FOR INSTALLATION, INSPECTIONS ON GREASE/ |
| | WATER SEPARATOR561-837- 4051 EXT. 4074 |
| | 6. PLEASE PROVIDE DETAIL/ SIZE FOR |
| | JUNCTION BOX AS SHOWN ON SHEET C-2 |
| | 7. PLEASE SHOW POINT OF CONFLICTS, WHERE |
| | WATER CROSSING SANITARY AND STORM WATER |
| | LINES AND INDICATE INVERTS/CROWNS ELEV. |
| | 8. PLEASE COORDINATE WITH PUBLIC |
| | UTILITIES ENGINEERING SERVICES FOR |
| | CONNECTING TO INLET.PROVIDE TWO SETS |
| | OF PLANS FOR THIER APPROVAL AND ACTUAL |
| | SERVICE CONNECTIONS. |
| | 9. PLEASE SHOW HORIZANTAL CLEARANCES |
| | BETWEEN THE SERVICE LINES. |
| | |
| | IF ANY QUESTIONS PLEASE CONTACT 561-569- |
| | 8096 EXT. 8492 |