| Plan Review Notes For Permit 98120351 |
| Permit Number |
98120351 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | A/C SCHEDULE DOES NOT REFLECT SAME AS | | | DRAWING I.E. 1&4 NOT 1&2 | | | NO EER SHOWN FOR AHU #4 | | | CFM VALUE FOR AHU #1 DOES NOT MATCH | | | MODEL NUMBER APPERANT TONNAGE | | | AHU #2 REQUIRES FAN SHUT DOWN BY DUCT | | | SMOKE DETECTOR | | | SEPARATE PERMIT REQUIRED FOR HOOD AND | | | SUPPRESSION SYSTEM FOR HOOD INCL.PLANS |
|