Plan Review Notes
Plan Review Notes For Permit 98120344
Permit Number 98120344
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SHOW CFM VALUES FOR ALL DROPS ON PLAN
 SHOW WHICH UNIT SUPPLIES VAULT A/C
 NEED OUTSIDE AIR CALCULATIONS PER ASHRAE
 62-89 ON PLAN
 NEED AIR BALANCE SCHEDULE PER 1994 SMC
 501.2 ON PLAN
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED FOR AHU 1,2, AND 3
 NCD APPR 2/18/99