Plan Review Notes
Plan Review Notes For Permit 98110675
Permit Number 98110675
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00*************** PROVISO ***************
  
 1)NOTE: STILL NEED TO SUBMIT AIC RATING
 OF EQUIPMENT MAINS. 110-9/215-5
 MAINS ARE TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT. AIC RATING CAN BE FIG.
 FORM FAULT CURRENT CALCULATIONS,
  
 2)NOTE: PLEASE INCLUDE A EQUIPMENT GRND
 FROM MAIN DISC TO PANEL.SIZE PER 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 BEFORE ANY ROUGH ELECTRICAL INSPECTION
 IS CALLED IN. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372