| Plan Review Notes For Permit 98110675 |
| Permit Number |
98110675 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************** PROVISO *************** | | | | | | 1)NOTE: STILL NEED TO SUBMIT AIC RATING | | | OF EQUIPMENT MAINS. 110-9/215-5 | | | MAINS ARE TO BE RATED FOR THE AVAILABLE | | | FAULT CURRENT. AIC RATING CAN BE FIG. | | | FORM FAULT CURRENT CALCULATIONS, | | | | | | 2)NOTE: PLEASE INCLUDE A EQUIPMENT GRND | | | FROM MAIN DISC TO PANEL.SIZE PER 250-122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | BEFORE ANY ROUGH ELECTRICAL INSPECTION | | | IS CALLED IN. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|