| Plan Review Notes For Permit 98110675 |
| Permit Number |
98110675 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | *************PROVISO******************** | | | | | | NEED TO SUBMIT AIC RATING OF EQUIPMENT. | | | NEED TO SUBMIT RISER DIAGRAM SHOWING | | | METER,PANEL,CONDUITS,WIRE SIZE. | | | WIRE SIZE 00 IS NOT A WIRE SIZE.!! | | | NEED TO SHOW ON RISER DIAGRAM GROUNDING | | | ELECTRODE SYSTEM GOING TO GRND.ROD, | | | C.W.P..ALL THYE ABOVE INFORMATION | | | REQ`D AS PER ART.215-5 | | | NOTE:LIGHT REQ`D OUTSIDE KITCHEN DOOR | | | AS PER ART.210-70 | | | NOTE:REQ`MENTS FOR KITCHEN PENINSULAR | | | AS PER ART,210-52-C-3 | | | NOTE:NEW MASTER BATH REQ`S GFI RECEPT. | | | ART.210-52D | | | NOTE:SMOKE DETECTORS REQ`D INSIDE AND | | | OUTSIDE BEDROOMS. | | | NOTE:NEW MASTER BEDROOM AREA OUTLET | | | SPACING AS PER 210-52A 2`6`12` RULE. | | | | | | ALL THE ABOVE INFORMATION MUST BE | | | SUBMITTED BEFORE ROUGH INSPECTION IS | | | CALLED IN. |
|