2001-01-08 00:00:00*************PROVISO********************
  
 NEED TO SUBMIT AIC RATING OF EQUIPMENT.
 NEED TO SUBMIT RISER DIAGRAM SHOWING
 METER,PANEL,CONDUITS,WIRE SIZE.
 WIRE SIZE 00 IS NOT A WIRE SIZE.!!
 NEED TO SHOW ON RISER DIAGRAM GROUNDING
 ELECTRODE SYSTEM GOING TO GRND.ROD,
 C.W.P..ALL THYE ABOVE INFORMATION
 REQ`D AS PER ART.215-5
 NOTE:LIGHT REQ`D OUTSIDE KITCHEN DOOR
 AS PER ART.210-70
 NOTE:REQ`MENTS FOR KITCHEN PENINSULAR
 AS PER ART,210-52-C-3
 NOTE:NEW MASTER BATH REQ`S GFI RECEPT.
 ART.210-52D
 NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOMS.
 NOTE:NEW MASTER BEDROOM AREA OUTLET
 SPACING AS PER 210-52A 2`6`12` RULE.
  
 ALL THE ABOVE INFORMATION MUST BE
 SUBMITTED BEFORE ROUGH INSPECTION IS
 CALLED IN.