| Plan Review Notes For Permit 98110234 |
| Permit Number |
98110234 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1- NEED PANEL SCHEDULES FOR ALL SHOWN | | | 2- NEED BRANCH CKT. #S ON PLAN TO SHOW | | | HOW MANY OUTLETS AND LIGHTS ARE TO BE | | | ON EACH CIRCUIT. | | | 3- NO A/C'S SHOWN ON ELECTRICAL DRAWINGS | | | SHOW SIZE OF WIRE AND PROTECTION. | | | 4- RISER DIAGRAM SHOWS NOT ENOUGH WIRES | | | IN SOME OF THE RACWAYS FOR 301,302, | | | 401,402,403,404,405,408,303,304,305, | | | 308. | | | 5- NEED LOAD CALC. AND SHOW SIZE OF WIRE | | | AND MAIN FOR GUTTER. |
|