| Plan Review Notes For Permit 98101449 |
| Permit Number |
98101449 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1- NORTH ELECTRICAL ROOM SHOWS MAINS #2, | | | 3 BEING 1200 AMPERES AND WIRE TO THEM | | | IS ONLY 1005 AMPERES | | | 2- SOUTH ELECTRICAL ROOM SAME AS ABOVE | | | ON MAIN #4 | | | 3- PANEL GPD HAS TWO SUBFEEDERS NEED TO | | | SHOW THE SIZE OF THE CONDUCTORS. | | | 4- NEED FAULT CURRENT ON ALL PANELS AND | | | SWITCH GEAR. 110-10,110-11 |
|