2001-01-08 00:00:00THESE COMMENTS APPLY TO ALL MODEL TYPES
  
 CLEANOUTS SHALL BE INSTALLED IN THE
 HORIZONTAL DRAINAGE PIPING PER SPC SEC.
 710.2.4.(1)(2).
  
 RISER NUMBERS ON SHT P-7 DON'T CORRELATE
 W/SHT.P-14.(SEE FLOOR PLAN D1.1.)SPC
 SEC.104.2.1.
  
 LOCATION OF FIXTURES ON RISERS S-1A,6,6A
 DOESN'T CORRELATE W/FLOOR PLAN ON SHT.P7
  
 SHT.P-20-RISERS S10 AND S9 ARE MIS-
 LABELED.(SEE SHT.P-7.WATER CLOSETS
 SHOULD BE LABELED AS S9,TUBS AND LAVS.AS
 S10.)
  
 REVISE FIXTURE UNIT LOAD FOR W/M RISERS.
 COMPLY W/TABLE 713.1.
  
 SIZE OF VENT STACKS FOR RISERS # 1,2,6,7
 9,11,13,14.SHALL COMPLY W/SPC SEC.911.3.
  
 PLANS SHALL BE SIGNED AND SEALED PER
 SBC SEC.104.2.2. AND SPC SEC.104.2.3
  
 MIN.SIZE OF DRAIN PAN RISER SHALL BE
 1 1/4" PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.507.8.3.(MIN.SIZE PAN DRAIN SHALL BE
 1" PER SPC SEC.507.8.2.)
  
 SUBMIT DETAILS FOR WOOD BLOCKING FOR
 FUTURE HANDICAP GRAB BAR INSTALLATION
 PER FEDERAL FAIR HOUSING ACT.
 AND 24 CFR 100.205.
  
 SHOW WIDTH OF SHOWERS IN ALL UNITS.
 COMPLY W/COUNTYWIDE AMENDMENTS TO SPC
 SEC.409.8.2.1.
  