| 2001-01-08 00:00:00 | THESE COMMENTS APPLY TO ALL MODEL TYPES |
| | |
| | CLEANOUTS SHALL BE INSTALLED IN THE |
| | HORIZONTAL DRAINAGE PIPING PER SPC SEC. |
| | 710.2.4.(1)(2). |
| | |
| | RISER NUMBERS ON SHT P-7 DON'T CORRELATE |
| | W/SHT.P-14.(SEE FLOOR PLAN D1.1.)SPC |
| | SEC.104.2.1. |
| | |
| | LOCATION OF FIXTURES ON RISERS S-1A,6,6A |
| | DOESN'T CORRELATE W/FLOOR PLAN ON SHT.P7 |
| | |
| | SHT.P-20-RISERS S10 AND S9 ARE MIS- |
| | LABELED.(SEE SHT.P-7.WATER CLOSETS |
| | SHOULD BE LABELED AS S9,TUBS AND LAVS.AS |
| | S10.) |
| | |
| | REVISE FIXTURE UNIT LOAD FOR W/M RISERS. |
| | COMPLY W/TABLE 713.1. |
| | |
| | SIZE OF VENT STACKS FOR RISERS # 1,2,6,7 |
| | 9,11,13,14.SHALL COMPLY W/SPC SEC.911.3. |
| | |
| | PLANS SHALL BE SIGNED AND SEALED PER |
| | SBC SEC.104.2.2. AND SPC SEC.104.2.3 |
| | |
| | MIN.SIZE OF DRAIN PAN RISER SHALL BE |
| | 1 1/4" PER COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.507.8.3.(MIN.SIZE PAN DRAIN SHALL BE |
| | 1" PER SPC SEC.507.8.2.) |
| | |
| | SUBMIT DETAILS FOR WOOD BLOCKING FOR |
| | FUTURE HANDICAP GRAB BAR INSTALLATION |
| | PER FEDERAL FAIR HOUSING ACT. |
| | AND 24 CFR 100.205. |
| | |
| | SHOW WIDTH OF SHOWERS IN ALL UNITS. |
| | COMPLY W/COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.409.8.2.1. |
| | |