| Plan Review Notes For Permit 98100755 |
| Permit Number |
98100755 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | THESE COMMENTS APPLY TO ALL MODEL TYPES. | | | | | | SUBMIT SANITARY AND WATER ISOMETRICS FOR | | | CAR WASH AND TRASH COMPACTOR AREAS PER | | | SPC SEC.104.2.1.(AN APPROVED INTERCEPTOR | | | SHALL BE INSTALLED PER SPC SEC.1004.5, | | | 1004.6. | | | | | | CLEANOUTS SHALL BE INSTALLED IN THE | | | HORIZONTAL PIPING PER SPC.SEC-710.2.4. | | | (1)(2). | | | | | | THE LABELING OF THE SANITARY RISERS ON | | | SHEETS P-1,P-13,P-14,P-15 DON'T | | | CORRELATE W/EACH OTHER. SPC SEC.104.2.1. | | | | | | INDICATE SLOPE OF PIPE ON PLANS.COMPLY | | | W/SPC TABLE 714.1,714.2. | | | | | | LOCATION OF FIXTURES ON SANITARY RISERS | | | SHALL MATCH THE ARCH.FLOOR PLANS.SPC | | | SEC.104.2.1. | | | | | | SHT.P-20-SIZE OF PAN DRAIN RISER SHALL | | | COMPLY W/COUNTYWIDE AMENDMENTS TO SPC | | | SEC.507.8.3. | | | | | | RELIEF VALVE DRAIN AND PAN DRAIN SHALL | | | NOT USE COMMON RISERS PER SPC SEC. | | | 507.8.4. | | | | | | FIXTURE UNIT LOAD FOR SANITARY RISERS | | | SHALL COMPLY W/SPC TABLE 713.1.(CHECK | | | W/M STACKS.) | | | | | | SIZE OF VENT STACKS FOR RISERS #1,2,6,7, | | | 9,11,13,14 SHALL COMPLY W/SPC SEC.911.1, | | | 911.3, AND TABLE 911.3. | | | | | | INDICATE TYPE OF OCCUPANCY OF BUILDING | | | ON PLANS.SEE STD.BLDG.CODE AND PLBG.CODE | | | SECS.104.2.3,AND 322.2 FOR REQ'S.FOR | | | SIGNED AND SEALED DRAWINGS. |
|