| Plan Review Notes For Permit 98100755 |
| Permit Number |
98100755 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | | | | THESE COMMENTS APPLY TO ALL MODEL TYPES | | | | | | 1) OVERFLOW PROTECTION REQUIRED ON ALL | | | AIR HANDLERS | | | 2) DRYER VENTS EXCEEDING 25' LENGTH ALL- | | | OWED PER CODE INCL. 5' DEDUCTION FOR EA. | | | 90 AND 2.5' DEDUCTION FOR EA. 45 DEGREE | | | BEND TO PROVIDE MANUFACTURES SPECS WITH | | | ALLOWED LENGTHS AND EQUIPMENT TO BE INS- | | | TALLED AT FINAL INSPECTION | | | 3) CONDENSER ACCESS TO COMPLY WITH SMC | | | AND NEC MIN. 36 INCHES FOR ELEC ACCESS | | | AND 24 INCHES FOR MECH | | | 4) ANY DIFFUSERS PENETRATING RATED CEIL- | | | INGS TO HAVE RATED FIRE DAMPERS INSTALL- | | | ED |
|