Plan Review Notes
Plan Review Notes For Permit 98100755
Permit Number 98100755
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************DENIED********************
  
 THESE COMMENTS APPLY TO ALL MODEL TYPES
  
 1) OVERFLOW PROTECTION REQUIRED ON ALL
 AIR HANDLERS
 2) DRYER VENTS EXCEEDING 25' LENGTH ALL-
 OWED PER CODE INCL. 5' DEDUCTION FOR EA.
 90 AND 2.5' DEDUCTION FOR EA. 45 DEGREE
 BEND TO PROVIDE MANUFACTURES SPECS WITH
 ALLOWED LENGTHS AND EQUIPMENT TO BE INS-
 TALLED AT FINAL INSPECTION
 3) CONDENSER ACCESS TO COMPLY WITH SMC
 AND NEC MIN. 36 INCHES FOR ELEC ACCESS
 AND 24 INCHES FOR MECH
 4) ANY DIFFUSERS PENETRATING RATED CEIL-
 INGS TO HAVE RATED FIRE DAMPERS INSTALL-
 ED