| Plan Review Notes For Permit 98100735 |
| Permit Number |
98100735 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | SANITARY AND WATER RISER SHALL CORRELATE | | | W/FLOOR PLAN.SPC 104.2.1. | | | | | | FIXTURES DISCHARGING DOWNSTREAM OF WATER | | | CLOSETS SHALL BE VENTED PER SPC SEC. | | | 913.2. | | | | | | WASHING MACHINES SHALL BE TRAPPED PER | | | SPC 1001.2. | | | | | | MIN.SIZE OF U/G DRAINAGE SHALL BE 2" PER | | | SPC SEC.714.4. | | | | | | MAIN VENT REQUIRED IN DRAINAGE SYSTEM | | | PER SPC SEC.904.3. | | | | | | INDICATE SLOPE OF PIPE FOR SANITARY | | | SYSTEM ON PLANS.COMPLY W/SPC SEC.714.1, | | | 714.2. | | | | | | HEAT TRAPS ARE REQ'D. ON THE WATER | | | HEATER PER FLA.ENERGY CODE SEC. | | | 612.1ABC.2.2. | | | | | | SUBMIT SYSTEM LISTING NUMBER FOR FIRE | | | RESISTANCE INTEGRITY OF PIPE PENETRATION | | | THROUGH RATED WALLS.COMPLY W/SBC.SEC. | | | 104.2.4. | | | | | | SANITARY ISOMETRIC SHOWS DRY VENTS. | | | CLARIFY.SPC.104.2.1. |
|