| Plan Review Notes For Permit 98100397 |
| Permit Number |
98100397 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | CLEARLY SHOW OCCUPANT LOAD OF STRUCTURE | | | PER SPC TABLE 407 TO ENSURE COMPLIANCE | | | FOR REQD.TYPES AND AMOUNT OF PLBG. | | | FIXTURES. | | | | | | TOILET STALLS SHALL COMPLY W/FACBC SEC. | | | 4.17.3.SEE EXCEPTION:NEW CONSTRUCTION. | | | SHOW CLEAR SPACE OF 60"DIAMETER FOR | | | WHEELCHAIR TURNING SPACE IN TOILET STALL | | | AND TOILET ROOMS PER FACBC SEC.4.2.3. | | | | | | WET VENTS SHALL RECEIVE DISCHARGE FROM | | | FIXTURE DRAINS ONLY.(WATER CLOSETS ON | | | 1ST.FLR CANNOT BE VENTED BY DRAIN TO 2ND | | | FLR.) | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | A PERMANENT LADDER AND PLATFORM SHALL BE | | | PROVIDED OR RELOCATE HTR. TO FLOOR. | | | SPC 501.7 | | | | | | SAFE WASTES NOT PERMITTED.INDIRECT WASTE | | | SHALL DISCHARGE INTO TOP OF FLOOR SINK. | | | PER SPC 804.1. | | | | | | DOOR ON HANDICAP STALL CANNOT SWING INTO | | | CLEAR FLOOR SPACE FOR FIXTURES PER FACBC | | | SEC.4.22.2.(SEE WOMEN'S R.R.) |
|