Plan Review Notes
Plan Review Notes For Permit 98100397
Permit Number 98100397
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00CLEARLY SHOW OCCUPANT LOAD OF STRUCTURE
 TO ENSURE COMPLIANCE W/TABLE 407 OF SPC
 FOR PLBG.FIXTURE REQS.
  
 TOILET STALLS SHALL COMPLY W/FACBC SEC.
 4.17.3.SEE EXCEPTION:NEW CONSTRUCTION.
 TOILET ROOMS SHALL COMPLY W/FACBC SEC.
 4.16.2.SHOW CLEAR SPACE OF 60"DIAMETER
 FOR WHEELCHAIR TURNING SPACE.
  
 H.C URINAL SHALL BE 17" A.F.F. ONE
 URINAL ON 1ST.FLR.SHALL COMPLY W/FACBC
 AND THE URINAL ON 2ND.FLR.SHALL COMPLY.
  
 WASTES FROM PREP OR RINSE SINKS SHALL BE
 INDIRECTLY WASTED TO FLOOR SINK(NO FLOOR
 DRAINS) PER SPC SEC.804.1.
  
 GREASE TRAP SHALL BE A MIN.OF 750 GALS.
 PER RULE 10D-6,F.A.C.AND CANNOT BE
 LOCATED IN BUILDING.
  
 A PAN AND DRAIN SHALL BE INSTALLED FOR
 THE GAS WATER HEATER PER COUNTYWIDE
 AMENDMENTS TO THE PLBG.CODE SEC.507.8.1,
 507.8.3.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 610.4.1, 610.4.2.
  
 WATER SERVICE SHALL BE EQUIPPED W/BACK-
 FLOW PREVENTION PER SPC SEC.601.
  
 VENTS SHALL NOT INCREASE IN SIZE PER
 SPC SEC.905.2(2" INCREASES TO 4")
  
 INDICATE TYPE OF GAS BEING SUPPLIED(LP
 OR NATURAL).SGC 302.
  
 GAS SUPPLY TO RANGE & CHAR-BROILER
 SHALL BE 1 1/4".
  
 WET VENTS SHALL RECEIVE DISCHARGE FROM
 FIXTURE DRAINS ONLY PER CITY OF WPB
 AMENDMENTS TO STANDARD PLBG.CODE SEC.
 911.1.
  
 AMOUNT OF PLBG.FIXTURES SHALL COMPLY W/
 FLA.STATUTE 553.141(3)(EQUAL NUMBER OF
 WATER CLOSETS FOR WOMEN AS COMBINED
 WATER CLOSETS AND URINALS FOR MEN.)